440R-C23139 Guardmaster MSR131RTP Safety Relay
product detail
Security Features
Dual channel input, can be connected to 2NC or 1NC contacts; Internal real-time detection of short circuits (cross faults) between channels
Once any channel is disconnected or a cross fault occurs, the 3-channel redundant safety normally open contacts (13-14, 23-24, 33-34) will immediately disconnect, and the 1-channel normally closed auxiliary contacts (41-42) will be used for status indication
Support automatic, manual, and monitoring reset:
- Automatic: Short circuit X1-X2, the fault disappears and recovers automatically
- Manual: Connect the normally open reset button in series in the X1-X2 circuit
- Monitoring: Connect the external contactor normally closed auxiliary point in series in the X1-X2 circuit to achieve welding monitoring
Electrical specifications
Power supply: 24V AC/DC universal (0.85-1.1 Un)
Safe output: 3NO, 2 A/250 V AC (AC-15), 2 A/30 V DC (DC-13)
Auxiliary output: 1NC, 2A
Response time: ≤ 30 ms; electrical lifespan 1 × 10 ? times
security level
ISO 13849-1 Cat.4 / PL e,IEC 61508 / EN 62061 SIL 3
Cross fault detection+dual channel redundancy to meet the highest PL e requirements
Installation and Environment
35mm DIN rail, shell 45mm wide, IP40 (body)/IP20 (terminals)
Working temperature -5...+55 ° C; humidity ≤ 90% RH, no condensation
Terminal torque 0.6 N · m, wire 0.2... 2.5 mm 2; An external 2 A gG fuse is required on the power supply side“