1420-V1A-ENT Powermonitor 500 Ethernetip Power Meter
product detail
Measurement and Accuracy
All electrical parameters including three-phase voltage, current, active/reactive/apparent power, power factor, frequency, and cumulative electricity (kWh/kVAh)
Electricity accuracy IEC 62053-22 Class 1 (1%), meeting billing and energy consumption allocation requirements
Communication and Integration
EtherNet/IP+Modbus TCP/IP dual protocol, supporting DLR/linear topology
4-channel configurable digital input/output (2-channel pulse output or alarm)
Automated Device Configuration (ADC) through Studio 5000 Logix Designer, plug and play
Electrical specifications
? Voltage input: 40-144 V LN/70-250 V LL (rated 240 V AC)
? Current input: 5 A CT (maximum 6 A)
? Auxiliary power supply: 100-240 V AC, 48-62 Hz, power consumption ≤ 27 VA
Installation and Display
96 × 96 mm panel opening, IP54 front cover, backlit LCD for on-site monitoring
DIN rail or panel fixation, depth