1411-8RL-162 Model 8Rl, 1600:5 Ratio
product detail
Rated transformation ratio: 1600 A: 5 A
Accuracy Class: ANSI Metrology Class B0.9 (± 0.3% accuracy), 60 Hz
Rated secondary load: 100 VA
Structure:
- Integrated solid annular iron core with circular window shape;
- Inner hole diameter 3.25 in (≈ 82.6 mm), can be directly threaded through busbars or cables;
- Insulation level 600 V, BIL 10 kV full wave impulse withstand.
Installation: Window insertion type, no additional bracket required; The secondary terminal is screw type, which is convenient for on-site wiring.
Application: Used in conjunction with PowerMonitor, PLC analog modules, energy meters, protective relays, etc., for monitoring and billing metering circuits in distribution cabinets, motor control centers, and plant feeder lines.
Environment: Operating temperature -20...+60 ° C; weight approximately 1.1 kg.